Heat that would be wasted, put to work.

Data centres spend money getting rid of heat; direct air capture plants spend money getting hold of it. Nordvar designs one site that does both jobs at once, built in phases: the data centre first, capture as its own permitted phase, alongside or after it depending on the financing of each phase. The five steps below show how, and the numbers that follow show what it saves.

Step 01

Compute

100%of the power becomes heat

Tenants run their workloads on servers in a compact, modular facility. All of the electricity those servers consume leaves them as heat; a server does no mechanical work, so there is nowhere else for the energy to go.

Step 02

Collect the heat

45–60 °Cwater off the racks

The servers are liquid-cooled. Cold plates on the chips and heat exchangers on the rack doors together deliver about 85% of the rack's heat into a closed water loop; the rest escapes to the room air. It is the design choice that makes everything downstream possible - and it cannot be added later.

Step 03

Raise the temperature

×3heat per unit of electricity, roughly

Server heat is warm, not hot. A heat pump lifts the water to around 100 °C, the temperature the capture process needs. The lift costs some power, which is why the site is designed around renewable electricity.

Step 04

Remove carbon

≈100 °Creleases the carbon dioxide

A direct air capture unit draws air through a material that binds carbon dioxide. Heated to around 100 °C, the material releases it as a concentrated stream. This is where the data centre's heat does its second job.

Step 05

Store it permanently

2 yrsto mineralise, in published Icelandic results

The concentrated carbon dioxide is dissolved and injected into basalt, where it reacts with the rock and becomes stone. Once mineralised, it does not return to the atmosphere. Storage is the default route. Where producers of synthetic fuels or carbon-based products exist near a site, captured CO₂ can also be supplied to them. Only stored tonnes are counted as removal; supplied tonnes are reported separately.

The gap, drawn to scale
020406080100120 °CAir-cooled exhaust30–40 °C · too cool to useLiquid-cooled water45–60 °C · warm enough to work withWhat capture needs≈100 °CHEAT PUMP · ×3020406080100120AC-E30–40 °CLC-W45–60 °CCN≈100 °CHEAT PUMP · ×3
  • AC-EAir-cooled exhaust - too cool to use
  • LC-WLiquid-cooled water - warm enough to work with
  • CNWhat capture needs - the heat pump bridges the gap

Energy, in numbers.

Every kilowatt-hour of electricity a server uses ends up as heat, and most data centres pay to get rid of it. Not all of it can be caught: liquid cooling collects the heat from the chips, and rear-door exchangers catch most of the rest, but some still escapes to the room air. A heat pump then raises the water in the loop to the temperature the capture process needs. The figures below follow one rack through a year.

One 10 kW rack, one yearheatelectricity
Electricity into the rack10 kW running continuously - 10 × 8,760 hours
87,600 kWh
Heat recovered into the water loopall of the rack's electricity leaves it as heat; cold plates and rear-door exchangers catch about 85% of it, the rest is lost to room air
about 75,000 kWh (about 85%)
Heat pump electricitya heat pump delivers three units of heat per unit of electricity; two of the three come from the recovered server heat
about 37,500 kWh
Process heat at ≈100 °Crecovered heat plus heat pump electricity
about 112,500 kWh
Capture unit electricityfans and vacuum - 0.5 to 0.7 MWh per tonne, measured and target values
about 17,000–50,000 kWh
÷ 1.5 to 3.3 MWh of heat per tonne of carbon dioxide - measured at commercial solid-sorbent plants, down to the published 2030 target
35–75tonnes of CO₂ a year - roughly, from one rack's recovered heat. The figure describes what that heat can support, not a Nordvar capacity.

What is saved

The saving is the heat that no longer has to be made from scratch. Delivering the same 112,500 kWh of process heat without server heat would take about 112,500 kWh of electricity with electric heating, or roughly 56,000 kWh with a heat pump drawing on cold outdoor air, because lifting heat from a few degrees is much harder than lifting it from fifty. Against that fairer comparison, one 10 kW rack saves in the order of 18,000 kWh of electricity a year; against electric heating, about 75,000 kWh.

The gain

The fair measure is electricity per tonne of CO₂ captured. The comparison below runs the same capture unit on different heat sources, using 2 MWh of heat and 0.5 MWh of capture electricity per tonne.

Electricity per tonne capturedheat pumpcapture unit
Electric heating
2.5 MWhabout 65% more
Heat pump from cold outdoor airCOP about 2
1.5 MWhbaseline
Server heat, upgradedCOP about 3 - the Nordvar case
about 1.2 MWhabout 20% less
Geothermal hot waterwhere available
0.5 MWhabout 65% less

Reusing server heat cuts the electricity needed per tonne by about 20% compared with the same unit on a conventional heat pump, and by about half compared with electric heating. The server heat itself is energy the tenant has already paid for; the capture process gets it for the cost of upgrading it. Where geothermal heat is piped in directly, it uses less electricity still, which is why a Nordvar site in a geothermal region uses both.

Where the larger gains are

One site, two products
The plot, the grid connection, the power contract, the fibre and the operations are paid for once and serve both the data centre and the capture unit.
The heat is already there
A standalone capture plant has to find heat, a data centre has to get rid of it. Putting them together removes a problem from each.
The customer pays for the heat
The tenant's electricity bill covers the server heat, so the removal is financed partly by compute revenue rather than entirely by credit sales.
Attribution is the product
Removal tied to a tenant's own energy use is something neither a standalone capture plant nor an ordinary data centre can offer.

One caveat: it is not lower-energy than capture running on geothermal heat. The energy gain of the method is real and modest; the gains above are what make a small site possible at all.

One loop, two jobs.

The water that carries heat away from the servers is the same water that feeds the heat pump. It leaves the racks at 45 to 60 °C, gives up its heat to the heat pump, and returns to the racks cooled to the temperature they need. When capture is running, the heat pump is therefore doing the data centre's cooling as a by-product, and the dry cooler that would otherwise reject the heat to the outside air can rest.

RacksHeat pump45–60 °CCooled, back to the racks≈100 °CTo captureDry cooler · rests
900–2,600kWh a year a 10 kW rack no longer spends on rejecting heat, roughly

The saving on the data centre side is the dry cooler's fan energy: typically 1 to 3% of the heat rejected. It is small, and we say so. It is also a further reason the two systems are designed as one loop rather than two: the compressor runs for the capture side, and the cooling comes free.

The dry cooler stays
Sized for the full load: capture will pause for maintenance, sorbent cycles or grid curtailment, and the servers must be cooled in those hours.
Control follows the servers
The heat pump is controlled on the temperature of the water returning to the servers, the dry cooler trims, and a buffer tank between them smooths the difference.
The balance flexes
When the capture unit needs more heat than the racks produce, the heat pump draws the balance from outside air or, where available, geothermal water; when it needs less, the dry cooler rejects the surplus.
In perspective
35 to 75tonnes of CO₂ a year, from the recovered heat of a single 10 kW rack: roughly the annual footprint of five to ten EU residents.
75,000kWh of heat recovered per rack that would otherwise be blown into the sky: about the yearly heating demand of five to seven homes in a cold climate (our estimate).
about 20%less electricity per tonne captured than the same unit running on a conventional heat pump.

Scaling

The arithmetic is linear. A 50 kW module supports roughly 170 to 375 tonnes a year on its recovered heat alone; a 1 MW site roughly 3,400 to 7,500 tonnes. These are heat-side figures. The capture unit and the heat pump draw electricity of their own, so a site's total power use rises when capture is added; what falls is the energy spent making heat that computing had already produced.

These are illustrative figures from published ranges and labelled estimates, not measurements. Nordvar will publish measured values once a site is operating.

Where the figures come from.
  1. 01Deutz, S. and Bardow, A. (2021). Life-cycle assessment of an industrial direct air capture process based on temperature–vacuum swing adsorption. Nature Energy 6, 203–213.DAC energy demand - measured and 2030 target
  2. 02International Energy Agency (2022). Direct Air Capture 2022: A key technology for net zero. IEA, Paris.Commercial DAC energy ranges
  3. 03Climeworks. Direct air capture technology: innovations in CO₂ removal. Official technology pages.Solid-sorbent capture, release at about 100 °C, mineral storage - operating in Iceland
  4. 04Jiang, J., Hu, B., Wang, R.Z. et al. (2023). High-temperature heat pump prototype, 50 °C source to 100 °C supply. Energy 263, Part D.Heat pump COP at the server-heat lift
  5. 05TLK Energy. Industrial heat pump guide.COP against temperature lift
  6. 06European Environment Agency (2024). Greenhouse gas emissions per capita, EU-27, 1990–2022.EU per-capita emissions, 2022
  7. 07Eurostat (2025). Greenhouse gas footprint per capita, EU, 2023. Dataset cli_gge_foot.EU consumption footprint, 2023
  8. 08Terlouw, T., Pokras, D., Becattini, V. and Mazzotti, M. (2024). Assessment of Potential and Techno-Economic Performance of Solid Sorbent Direct Air Capture with CO₂ Storage in Europe. Environmental Science & Technology.DAC potential and cost in Europe
  9. 09Schneider Electric / DCD (2024). Direct Liquid Cooling System Challenges in Data Centers. White Paper 210.Heat capture ratio - share to liquid vs air
  10. 10Reviews of absorption and compression heat pumps for industrial heating. City University of Hong Kong; Heat Pumping Technologies.Heat pumps at large temperature lifts

Designed as one system

Each part of the chain exists today. Nordvar does not build the capture unit or the storage; both come from established operators - the capture technology itself was developed by a prominent company and is already operating at commercial scale. What Nordvar adds is the decision to design a data centre from the start as the heat source for carbon removal. A facility built this way can operate as a data centre first and add capture as a second phase, without rebuilding.

Liquid cooling
Chosen at the start. It cannot be retrofitted, and everything downstream depends on it.
Heat-loop connections
Points where the capture unit's supply plugs in, built into the module from day one.
Space and power reserved
Room on the plot and margin in the connection for the capture phase.
Storage within reach
A location where mineral storage exists, so captured carbon travels a short distance.

What it is not

Nordvar does not offset. The carbon removed is measured, verified and stored permanently, and it is counted once. CO₂ supplied for reuse is not counted as removal. The data centre itself runs on renewable electricity; the capture process removes carbon from the atmosphere in addition to that, it does not cancel emissions from elsewhere.